Comparable to Axis Thermal renowned
Dual Fuel High Velocity Burner.
DUAL-FUEL
Natural gas and/or light oil.
WIDE STABILITY RANGE
From 15% excess fuel to 400% xces air.
UNIT CONSTRUCTION
The high temperature tile is secured in the main
body section - no extra support is required.
USEFUL CAPACITY RANGES
Ratings from 05.mkcal to 6.4mkcal / hr
EASY INSPECTION / SERVICE
Air and gas piping need not be removed for
complete access to internals.
PREHEATED AIR CAPABILITY
To 400o C main air temperature at the burner
List 1. Main and Atomizing Air Capacities Scfh* (Standard Cubic Feet per Hour)
Burner
Fuel
Main Air
Atomizing Air (with 16osi main air)
Flame Lengths
In millimeter
0.2
1
4
9
16
12”wg (Gas)
60”wg (Oil)
18” Main Air
3435 – 1A
Gas
65
240
545
870
1220
75
180
220
Oil
85
232
545
865
1200
3435– 2A
Gas
170
500
1090
1660
2280
30
140
200
Oil
165
430
1070
1660
2280
3435– 3A
Gas
235
680
1530
2490
3420
70
180
300
Oil
300
665
1430
2320
3180
3435– 4A
Gas
545
1270
2830
4350
6050
160
390
500
Oil
665
1240
2750
4310
5850
3435– 5A
Gas
895
2080
4460
6950
9500
400@27”wg
585
550
Oil
895
2110
4760
7450
10000
3435– 6A
Gas
1000
3500
7100
11300
15200
380@27”wg
470
960
Oil
1200
3800
7400
11200
15000
List 2 . Main and Atomizing Air Scfh Capacities
Main Air
Atomizing Air
(with 27” wg Main Air)
Burner
At 27”wg
At 12”wg
At 60 ”wg
3435-1A
1350
90
180
3435-2A
3000
90
190
3435-3A
4120
100
200
3435-4A
7240
240
460
3435-5A
12100
430@27”wg
590
3435-6A
17500
430@16”wg
590
List 3. Maximum %XS Air
(27”wg Main Air)
Burner Size
Fuel
-1
-2
-3
-4
-5
-6
Natural Gas
400
400
400
350
350
600
Light oil
200
300
400
300
350
600
OTHER PRODUCTS
Excess Air Gas Burner 1422
Fire All Gas Burner 1514
Gas Burner 1562
HF Burner 001
Excess Air Light Oil Burner 2422
Fire All Heavy Oil Burner 2514
Furnace Oil Burner 2562
HF Burner 002
High Velocity Oil Burner 2435
Excess Air fuel/Gas Burner 3422
Fire All Dual Fuel Burner 3514
Dual Fuel High Velocity Burner 3435
Dual Fuel Burner 3562
HF Burner 003
NOTE : Dimensions shown are subject to change. please obtain certified prints from Axis Thermal Engineering Company. If space limitations or other considerations make exact dimension(s) critical.
WARNING: Situations dangerous to personnel and property can develop from incorrect operation of combustion equipment. Axis Thermal urges compliance with National Safety Standards and Insurance Underwriters recommendations, and care in operation.