1562 Gas Burners are designed to give maintenance-free operation using heavy oil, light oil, or gas. There are no “Superfluities” on this burner—it has a heavy cast iron body of clean design that avoids clogging even when used on tough jobs such as forge furnaces fired with heavy oil.
Burner Competency
The total air capacity of the burners is listed under list I for single blower supplying at 20”wg combustion air and
22”wg atomizing air for light oil operation and 22”wg combustion air and 38”wg atomizing air for heavy furnace oil
operation. Use list II and III when selecting separate blowers for combustion and atomizing air. For sizing blowers or
burners at other pressures, add figures from the List II and III to get total capacity.
Capacities shown in list II is for operation on gas with the air shuttled
closed. On oil operation these capacities are increased 20% the
additional air supplied through the atomizing air connection. When
burning either gas or oil with the shutter open, burner capacities
may be doubled if furnace conditions assure sufficient secondary air.
|
Functions of the Burner
Oil with a viscosity of 70 to 90 seconds Redwood I and a pressure
between 25 and 30 psi, should be supplied to an Air/Oil ratio
controller which will deliver oil to the burner at a pressure
proportional to the main air pressure, thus maintaining the correct
air/oil ration at all firing rates. The atomizing air pressure at the
burner may be as low as 21”wg when using distillate oil, 38”wg
when using heavy oil.
The 1562 burners can operate on any gas of 2000 to 12800 kcal per
cu.ft heating value. Switching from gas to oil operation or oil to gas
may be done quickly without furnace shutdown, simply by turning
off one fuel valve and opening the other. |
Burner Assembly
The heavy cast iron body can stand much abuse. All internal parts of the 1562 burner are machined. The smooth
surfaces stay free of oil deposits and dirt, thus greatly minimizing the need for cleaning, oil is, put though the burner
in a straight passage having a large cross-sectional area permitting visual inspection for clogging and easy clean out if
necessary. The burner oil valve is a non-plugging V-port oil valve which produces small and uniform flow rate changes
throughout the180oC sweep of the control handle.
LIST I. AIR CAPACITIES in CFH |
| Burner Designation |
1562-3A |
1562-4A |
1562-5A |
| Air Pressures at Burner |
Combustion 24”wg; Atomising 28”wg |
4735 |
5935 |
10630 |
| Combustion 40 ”wg; Atomising 44 ”wg |
6320 |
7670 |
13640 |
LIST II. COMBUSTION AIR CAPACITIES in CFH |
| Burner Designation |
Air pressure at Burner in inches of WGP |
| 1 |
2 |
3 |
5 |
7 |
9 |
10 |
14 |
17 |
21 |
24 |
28 |
35 |
| 1562-3A |
575 |
1150 |
1625 |
1900 |
2300 |
2575 |
2815 |
3250 |
3635 |
3800 |
4300 |
4600 |
5150 |
| 1562-4A |
725 |
1450 |
2050 |
2500 |
2900 |
3250 |
3525 |
4100 |
4580 |
5000 |
5420 |
5800 |
6500 |
| 1562-5A |
1156 |
1156 |
3270 |
3270 |
4625 |
5175 |
5660 |
6540 |
7300 |
8000 |
8650 |
9250 |
10350 |
LIST III. ATOMISING AIR CAPACITIES in CFH |
| Burner Designation |
Air pressure at Burner in inches of WGP |
| 24 |
28 |
31 |
35 |
38 |
41 |
| 1562-3A |
935 |
1000 |
1060 |
1120 |
1170 |
1220 |
| 1562-4A |
935 |
1000 |
1060 |
1120 |
1170 |
1220 |
| 1562-5A |
2630 |
2980 |
2980 |
3150 |
3290 |
3430 |
| NOTE: Dimensions shown are subject to change. please obtain certified prints from
Axis Thermal Engineering Company. If space limitations or other considerations
make exact dimension(s) critical. |
| |
| WARNING: Situations dangerous to personnel and property can develop from incorrect operation of combustion equipment. Axis Thermal urges compliance with National Safety Standards and Insurance Underwriters recommendations, and care in operation. |
|